- Toroidal design.
- Supplied with 24" insulated secondary leads, terminated with crimped ring connectors.
- Suitable for use with bare (uninsulated) primary conductor in circuits up to 600 V (4 KV hipot); or at higher voltages when a suitably insulated conductor is used.
- All units have 5 A secondary for use with standard AC ammeters with 5 A movements.
- Two hole mounting bracket on all models.
- UL #E227616 volume #1 file #X0DW2.
To obtain current measurement:
- Pass the wire carrying the current to be measured through the window of the CT transformer (acting as a primary winding).
- Connect the CT secondary to an ammeter with a 5 amp movement.
For higher accuracy or higher VA burden rating:
- Choose a CT with a primary which is a multiple of the required primary rating and which has the accuracy or VA burden you require.
- Loop the wire carrying the current to be measured through the window a number of times equal to the multiple. This "winding" will reduce the ratio back to required primary rating.
- Example "A": To obtain an accuracy of 1.2% at 10 VA burden with a ration of 100:5, use a CT400A and loop 4 primary turns through the window.
- Example "B": To obtain a 25:5 ratio, use a CT75A with 3 primary turns to yield 2% accuracy or a CT50A with 2 primary turns to yield 3.2% accuracy.